For medium-voltage (about 11–33 kV) distribution switchgear, the circuit breakers now most widely used are:
सही उत्तर: ग) vacuum circuit breakers
Vacuum interrupters need little maintenance and have excellent arc-quenching at medium voltages; SF₆ dominates at higher transmission voltages.
💬 टिप्पणी / गल्ती रिपोर्ट (०)
-
Differential protection of a transformer or generator operates on the principle of:
सही उत्तर: घ) comparing the currents entering and leaving the protected zone
Under normal conditions or external faults the two currents balance; an internal fault upsets the balance and operates the relay.
💬 टिप्पणी / गल्ती रिपोर्ट (०)
-
An overcurrent relay is set at 100% of its 5 A rating and fed from a 400/5 A CT. For a fault current of 4000 A, the plug setting multiplier (PSM) is:
सही उत्तर: ख) 10
Relay current = 4000 × 5/400 = 50 A; PSM = 50/(1.0 × 5) = 10.
💬 टिप्पणी / गल्ती रिपोर्ट (०)
-
Series reactors (current-limiting reactors) are installed in power systems mainly to:
सही उत्तर: क) limit the short-circuit current
Their reactance adds to the fault path, limiting fault current to a level the breakers can interrupt.
💬 टिप्पणी / गल्ती रिपोर्ट (०)
-
In power systems, the most frequently occurring type of fault is:
सही उत्तर: ग) the single line-to-ground fault
About 70–80% of faults on overhead lines are single line-to-ground (e.g. flashover of one insulator); symmetrical three-phase faults are the rarest.
💬 टिप्पणी / गल्ती रिपोर्ट (०)
-
A generator reactance is 0.1 pu on its own 10 MVA rating. On a 50 MVA base at the same voltage, its per-unit reactance is:
सही उत्तर: ख) 0.5 pu
Z_new = Z_old × (MVA_new/MVA_old) × (kV_old/kV_new)² = 0.1 × 50/10 = 0.5 pu.
💬 टिप्पणी / गल्ती रिपोर्ट (०)
-
A 10 MVA transformer has a reactance of 10% (0.1 pu). Ignoring source impedance, the fault level for a three-phase fault at its terminals is:
सही उत्तर: क) 100 MVA
Short-circuit MVA = base MVA/Z_pu = 10/0.1 = 100 MVA.
💬 टिप्पणी / गल्ती रिपोर्ट (०)
-
On a base of 10 MVA and 11 kV, an impedance of 6.05 Ω expressed in per unit is:
सही उत्तर: ख) 0.5 pu
Base impedance = kV²/MVA = 121/10 = 12.1 Ω, so Z_pu = 6.05/12.1 = 0.5.
💬 टिप्पणी / गल्ती रिपोर्ट (०)
-
An arc suppression coil (Petersen coil) connected between the neutral and earth is used in:
सही उत्तर: ग) resonant earthing of the neutral
The coil's inductance is tuned to the line's capacitance to earth, so the capacitive earth-fault current is neutralised and arcing faults self-extinguish.
💬 टिप्पणी / गल्ती रिपोर्ट (०)
-
A 'wave trap' (line trap) installed at a substation on a transmission line is used for:
सही उत्तर: क) power line carrier communication (blocking high-frequency carrier signals from entering the station)
The wave trap is a parallel-tuned circuit offering high impedance to the carrier frequency while passing 50 Hz power current.
💬 टिप्पणी / गल्ती रिपोर्ट (०)